Quick Ship: Duplex Pump Control Panel - Three Phase (TPDXX)

For higher flow rate systems, M-Tech Control’s Duplex control panels offer dependable control of dual pump applications across a multitude of industries. Our pump panels are UL508A certified and assembled using Schneider Electric / Square-D components. Three-Phase Duplex control panels are available in 208/230 Volt, 460V and 575 Volt configurations.

Each Duplex panel comes with M-Tech’s exclusive 3-year limited warranty. We truly stand behind our products.

Each Panel can be enclosed in your choice of NEMA 4 ANSI 61 painted cold rolled steel, NEMA 4X stainless steel and NEMA 4X non-metallic enclosures.  Our Duplex panels can be selected in the configurator below.

View Our Product Catalog

Panels include the following as standard:

  • Main disconnect for (2) three phase pump motors.
  • Through the door rotatory disconnect handle. Padlockable for lock out/tag out
  • (2) Motor contactors
  • (2) Motor protection switch with overload for three phase motors.
  • Control circuit breaker
  • Control for 2 pumps.
  • 2) Hand-Off-Auto switch. (Located on panel door)
    • Hand – Runs continuously bypassing float switches.
    • Auto – Keeps water level between 2 floats. 2 floats required for each pump. (4 floats total) Each pump will be mounted in a separate tank. Floats not included.
  • Numbered terminal blocks for wiring of float switches
  • Ground Lugs
  • NEMA 4/12 ANSI 61 painted cold rolled steel, NEMA 4X 304 Stainless Steel, or NEMA 4X non-metallic corrosion resistant enclosures are available. (316 S/S upon request)
  • All panels are UL listed for the United States and Canada cUL508A

Options

  • Green pump run pilot light for each pump.
  • High Water Alarm – Float switch not included
  • Red alarm beacon.
  • Auxiliary Dry Contact.
  • Float Switch.

Basic Sequence of Operation

2 pumps working independently

  • In Auto – As liquid level rises, the upper float switch closes and turns on pump
  • As liquid is pumped down and level goes below the stop float switch, the pump will turn off.
  • Off – Pump Off
  • Hand – Pump on continuously until switch is turned off

Please contact M-Tech for additional technical and volume price information.

We also offer custom configurations.

skupump quantityvoltagecoil voltagehp ratingenclosure typeenclosure sizepriceQuick ShipQuote

Contact Us

Contact our team of experts today for a customized quote!